INDUSTRIAL ENERGY STATION SOLUTION PLATFORM
STEP 1 / EDIT P&ID → STEP 2 / GENERATE 3D PLANT
工业能源站整体解决方案平台
系统流程方案已生成
66%WHEEL TO ZOOM · DRAG EMPTY SPACE TO PAN · 2000 × 1100
LEGENDPROCESS LINE / TEMPERATURE20 50 80 130 °C┄┄ SIGNAL LINETT FIELD INSTRUMENT◇ STREAM NUMBER
EKEUROKLIMATSINCE 1963 · INDUSTRIAL ENERGY EPC
FAL-01 Dyeing · Wastewater Heat-Pump Hot-Water SystemFAL-01 · WASTEWATER HEAT-PUMP HOT-WATER SYSTEM
P&IDDWG EK-FAL-HP-PID-001 · REV A
PROCESS / TEMPERATUREINSTRUMENT SIGNALINLET PORTOUTLET PORT→ 流向32 LINES · 34 SYMBOLS
04管路与热质平衡表由原理图实时生成 · 19
| 流股 | 说明 | 起点 → 终点 | 介质 | 设计温度 | 流量 | 管路规格 |
|---|---|---|---|---|---|---|
| S-01 | Hot drains from FAL-01 | FAL-01 → TCV-100 | HOT | 55.0 °C | 50.0 m³/h | OPEN DRAIN CHANNEL · 800 mm |
| S-02 | Cold drains below 40 °C bypass | TCV-100 → ETP | WATER | 38.0 °C | 50.0 m³/h | DN150 · HDPE gravity |
| S-03 | Hot drains to rotary screen | TCV-100 → F-101 | HOT | 55.0 °C | 50.0 m³/h | OPEN DRAIN CHANNEL · 800 mm |
| S-04 | Screened wastewater to Stage 1 | P-101A/B → HX-101 | HOT | 55.0 °C | 50.0 m³/h | DN100 · SS304 |
| S-05 | Wastewater Stage 1 to source HX | HX-101 → HX-102 | WATER | 40.9 °C | 50.0 m³/h | DN100 · SS304 |
| S-06 | Cooled wastewater to ETP | HX-102 → ETP | COLD | 25.0 °C | 50.0 m³/h | DN100 · SS304 |
| S-07 | Soft-water make-up | LCV-305 → HX-101 | COLD | 30.0 °C | 35.0 m³/h | DN100 · SS304 |
| S-08 | Pre-heated soft water to tank | HX-101 → TK-301 | HOT | 50.0 °C | 35.0 m³/h | DN100 · SS304 |
| S-09 | Hot cooling-water return | FAL-01 → TK-301 | WATER | 47.5 °C | 4.0 m³/h | DN100 · SS304 |
| S-10 | Charge water to HP-B condenser | P-301A/B → HP-B | HOT | 49.7 °C | 39.0 m³/h | DN100 · SS304 |
| S-11 | Between HP-B and HP-A condensers | HP-B → HP-A | HOT | 62.7 °C | 39.0 m³/h | DN100 · SS304 |
| S-12 | HP-A leaving water | HP-A → HX-103 | HOT | 80.0 °C | 39.0 m³/h | DN100 · SS304 |
| S-13 | To tank hot zone | HX-103 → TK-301 | HOT | 80.0 °C | 39.0 m³/h | DN100 · SS304 |
| S-14 | Hot-water header to FAL-01 | P-302A/B → FAL-01 | HOT | 80.0 °C | 39.0 m³/h | DN100 · SS304 |
| S-15 | High-stage source return | HP-A → HX-102 | WATER | 37.9 °C | 43.5 m³/h | DN100 · SS304 |
| S-16 | Heat-pump source cascade | HP-B → HP-A | COLD | 30.1 °C | 43.5 m³/h | DN100 · SS304 |
| S-17 | Source water to HP-B | P-151A/B → HP-B | COLD | 22.0 °C | 43.5 m³/h | DN100 · SS304 |
| S-18 | Controlled high-temperature supply to Stage 3 | TCV-401 → HX-103 | STEAM | 120.0 °C | 10.0 m³/h | DN80 · SS304 |
| S-19 | Stage-3 return to boiler economizer | PSV-401 → E-02 | HOT | 80.6 °C | 10.0 m³/h | DN80 · SS304 |
05设备清单与选型由原理图实时生成 · 46
| 位号 | 用途 | 设计参数 | 供货范围 |
|---|---|---|---|
| FAL-01 | JET DYEING MACHINES | 520 kW · 47.5 °C · 3 bar · 6 ports · machines: 4 · process: Jet dyeing | EUROKLIMAT EPC |
| TK-300 | SOFT WATER TANK | 150 kW · 30 °C · 2 bar · 4 ports · volume: 50 · waterQuality: WTP soft water | EUROKLIMAT EPC |
| TK-101 | HOT WASTEWATER SUMP | 60 kW · 55 °C · 1 bar · 4 ports · volume: 60 · residenceTime: 72 | EUROKLIMAT EPC |
| F-101 | ROTARY DRUM SCREEN | 60 kW · 55 °C · 2 bar · 2 ports · screenOpening: 0.5 mm · material: SS304 | EUROKLIMAT EPC |
| P-101A/B | WASTEWATER TRANSFER PUMPS | 15 kW · 55 °C · 4 bar · 4 ports · duty: Duty / standby · flow: 55 · head: 25 | EUROKLIMAT EPC |
| HX-101 | STAGE-1 PRE-HEAT EXCHANGER | 808 kW · 50 °C · 10 bar · 4 ports · area: 59 · LMTD: 7.6 | EUROKLIMAT EPC |
| HX-102 | SOURCE ISOLATION EXCHANGER | 908 kW · 39.1 °C · 10 bar · 4 ports · area: 168 · approach: 3 | EUROKLIMAT EPC |
| P-151A/B | SOURCE LOOP PUMPS | 22 kW · 22 °C · 4 bar · 4 ports · duty: Duty / standby · flow: 43.5 · head: 28 | EUROKLIMAT EPC |
| HP-B | LOW STAGE HEAT PUMP | 720 kW · 59.9 °C · 10 bar · 4 ports · stage: Low stage · COP: 4.6 · sourceInlet: 22 · sourceOutlet: 30.1 | EUROKLIMAT EPC |
| HP-A | HIGH STAGE HEAT PUMP | 760 kW · 80 °C · 10 bar · 4 ports · stage: High stage · COP: 4.2 · hotWaterInlet: 62.7 · hotWaterOutlet: 80 | EUROKLIMAT EPC |
| HX-103 | Stage 3 | 420 kW · 75.6 °C · 10 bar · 4 ports · stage: 3 · duty: 420 | EUROKLIMAT EPC |
| TK-301 | STRATIFIED HOT-WATER TANK | 150 kW · 80 °C · 4 bar · 6 ports · volume: 150 · stratified: Yes | EUROKLIMAT EPC |
| P-301A/B | HEAT-PUMP CHARGE PUMPS | 24 kW · 49.7 °C · 4 bar · 4 ports · duty: Duty / standby · flow: 39 · head: 30 | EUROKLIMAT EPC |
| P-302A/B | HOT-WATER DISTRIBUTION PUMPS | 24 kW · 80 °C · 4 bar · 4 ports · duty: Duty / standby · flow: 39 · head: 32 | EUROKLIMAT EPC |
| E-02 | BOILER FLUE-GAS ECONOMIZER | 360 kW · 120 °C · 10 bar · 4 ports · flueGasInlet: 130 · flueGasOutlet: 110 | EUROKLIMAT EPC |
| Boiler-02 | 10 t/h | 560 kW · 145 °C · 10 bar · 4 ports · steamCapacity: 10 t/h · efficiency: 94 | EUROKLIMAT EPC |
| ETP | EXISTING EQUALISATION | 120 kW · 25 °C · 1 bar · 4 ports · status: Existing · inletTemperature: 25 | EUROKLIMAT EPC |
| TCV-100 | Hot/cold drain diverter | < 40 °C bypass | EUROKLIMAT EPC |
| LCV-305 | Tank level control valve | controlValve | EUROKLIMAT EPC |
| TCV-401 | Motorized shut-off valve | motorizedValve | EUROKLIMAT EPC |
| PSV-401 | Pressure safety valve | safetyValve | EUROKLIMAT EPC |
| FT-301 | Soft-water make-up flow | 35.0 m³/h | EUROKLIMAT EPC |
| TT-308 | Cooling-water return | 47.5 °C · 4.0 m³/h | EUROKLIMAT EPC |
| TT-100 | Hot drain temperature | 55.0 °C | EUROKLIMAT EPC |
| LT-101 | Sump level | LSL / LSLL | EUROKLIMAT EPC |
| TT-101 | Sump temperature | 55.0 °C | EUROKLIMAT EPC |
| PDT-102 | Filter differential pressure | pressure | EUROKLIMAT EPC |
| FT-101 | Wastewater flow | 50.0 m³/h | EUROKLIMAT EPC |
| TT-102 | Stage-1 outlet | 40.9 °C | EUROKLIMAT EPC |
| TT-103 | ETP inlet | 25.0 °C | EUROKLIMAT EPC |
| TT-153 | Source inlet | 22.0 °C | EUROKLIMAT EPC |
| TT-152 | Interstage source | 30.1 °C | EUROKLIMAT EPC |
| TT-151 | Source return | 37.9 °C | EUROKLIMAT EPC |
| FT-302 | Heat-pump charge flow | 39.0 m³/h | EUROKLIMAT EPC |
| TT-302 | Charge temperature | 49.7 °C | EUROKLIMAT EPC |
| TT-303 | Cascade temperature | 62.7 °C | EUROKLIMAT EPC |
| TIC-304 | High-stage setpoint | SP 75.6 °C | EUROKLIMAT EPC |
| TIC-305 | Boiler setpoint | SP 80.0 °C | EUROKLIMAT EPC |
| TT-401 | Flue-gas inlet | 120 °C | EUROKLIMAT EPC |
| TT-402 | Economizer outlet | 80.6 °C | EUROKLIMAT EPC |
| PIC-307 | Distribution pressure control | pressureController | EUROKLIMAT EPC |
| FQ-307 | Hot-water totalizer | 39.0 m³/h at 80 °C | EUROKLIMAT EPC |
| TT-306A | Tank hot zone | 80.0 °C | EUROKLIMAT EPC |
| TT-306B | Tank upper zone | temperature | EUROKLIMAT EPC |
| TT-306C | Tank middle zone | temperature | EUROKLIMAT EPC |
| TT-306D | Tank cold zone | 49.7 °C | EUROKLIMAT EPC |
PFD / 17 台 / 套设备32 条工艺连接1,200 kW工艺蓝图已就绪
EEngineeringPProcurementCConstructionOOperation